General: Controller does not regulate or the cooling relays do not activate although setpoints and hysteresis are exceeded!

1. Is there a consumer lock active on the VS (controller data screen)? The Refrigeration System Number. on the case controller concerned can be set to "---" or any unassigned Refrigeration System Number for the test.
2. End defrosting (e.g. by restarting)
3. - Is the correct controller type configured (check DIP switch)?
- If the configured controller type not present in the controller (UA 410 L; D; E; )
4. , contact manufacturer

Possible causes:
for 1. consumer lock via VS
for 2. defrost is running
for 3. incorrect controller type configured
for 4. defective control component 

General: Controller does not regulate or the cooling relays do not activate although setpoints and hysteresis are exceeded!

1. Is there a consumer lock active on the VS (controller data screen)? The Refrigeration System Number. on the case controller concerned can be set to "---" or any unassigned Refrigeration System Number for the test.
2. End defrosting (e.g. by restarting)
3. - Is the correct controller type configured (check DIP switch)?
- If the configured controller type not present in the controller (UA 410 L; D; E; )
4. , contact manufacturer

Possible causes:
for 1. consumer lock via VS
for 2. defrost is running
for 3. incorrect controller type configured
for 4. defective control component 

General: Controller does not regulate or the cooling relays do not activate although setpoints and hysteresis are exceeded!

1. Is there a consumer lock active on the VS (controller data screen)? The Refrigeration System Number. on the case controller concerned can be set to "---" or any unassigned Refrigeration System Number for the test.
2. End defrosting (e.g. by restarting)
3. - Is the correct controller type configured (check DIP switch)?
- If the configured controller type not present in the controller (UA 410 L; D; E; )
4. , contact manufacturer

Possible causes:
for 1. consumer lock via VS
for 2. defrost is running
for 3. incorrect controller type configured
for 4. defective control component 

Erklärung:

Jeder User des EDP hat einen zusätzlichen Cloud-Speicher. Innerhalb der OwnCloud können Pfade erstellt werden, die hierüber mit einer EDP-Komponente verknüpft werden.

Auf diese Weise sind z.B. Massen-Uploads ins EDP möglich, d.h. es können beliebig viele Dokumente in den Pfad der OwnCloud kopiert werden, die dann automatisch in die zugeordnete Komponente im EDP synchronisiert werden.