General: Why does the "No Defrost" error message occur although the "No Defrost" parameters for suppression of this alarm has been set to "--" ?

The "No Defrost" parameter in the Menu 6 Configuration - 3 Alarm Delay is not applied until another defrost has taken place after the adjustment. If the value of this parameter has been set to "--", the next defrost must be waited for or a manual defrost must be initiated so that afterwards no alarm will be generated. 

General: Why does the "No Defrost" error message occur although the "No Defrost" parameters for suppression of this alarm has been set to "--" ?

The "No Defrost" parameter in the Menu 6 Configuration - 3 Alarm Delay is not applied until another defrost has taken place after the adjustment. If the value of this parameter has been set to "--", the next defrost must be waited for or a manual defrost must be initiated so that afterwards no alarm will be generated. 

General: Why does the "No Defrost" error message occur although the "No Defrost" parameters for suppression of this alarm has been set to "--" ?

The "No Defrost" parameter in the Menu 6 Configuration - 3 Alarm Delay is not applied until another defrost has taken place after the adjustment. If the value of this parameter has been set to "--", the next defrost must be waited for or a manual defrost must be initiated so that afterwards no alarm will be generated. 